TECHNICAL INFORMATION
Protection class IP 20
Operating temperature 0 ºC…+50 ºC
Storing temperature -20 ºC…+70 ºC
Power supply
Operating voltage24 Vac/Vdc (-10 % ... +20 %) , 50/60 Hz
Power required 4 VA/ 2,5 W
Data transfer connections
RS-485 bus (A and B)Galvanically isolated, supported protocols
Modbus-RTU
Relay control
R(1...4) 4 pcs change-over contact relays,
230Vac/4 (1) A eller 24Vdc/4 (1)A.
Resistive load is 4A, inductive load is 1A
(cos Ø = 0.8)
Approvals
EMC-directive 2014/30/EU
- Interference immunity EN 61000-6-2
- Interference emissions EN 61000-6-3
Small voltage directive 2014/35/EEC
-Safety EN 60730-1
Ouman Oy recommends that 24 V and 230 V connections are not used in
the same module. If the same module includes 24 V and 230 V connections,
external cables must be installed in such way the loose cable doesn
`t cau-
se a risk. ( E.g. the risk can be avoided by binding the cables or using cable
duct near the terminals to ensure cables stay in the connector).
Cable stripping length 10 mm.
Terminal resistor and biasing resistors
The device uses a galvanically isolated RS-485 network as a physical
interface. Only one device at a time can write in to the network, the other
devices are listening. For this reason there are situations when no device
writes in to the network but they all are listening. The biasing resistors
ensure that the network remains stable in this situation. This is especial-
ly important if the network is long and if there is external interference.
Terminal resistors and biasing resistors must be taken into use in two
(and only two) devices per network. The devices in question must be po-
sitioned at both ends of the network
If this device is first or last device in the network, take the resistors into use.
RS-485 bus connections (see page 9)
A Connector is duplicated bus in order to facilitate concatenation (93, 96)
B Connector is duplicated bus in order to facilitate concatenation (94, 97)
BG RS-485 bus isoloited ground (95, 98)
Terminal (T) and biasing resistors (BIAS) DIP
Terminal resistor and biasing resistors are not in use
Terminal resistor is in use
Biasing resistors are in use
1 2 3
When you press the PRG button for more than 5 seconds, the unit re-
sets and resets the factory settings.
7
24 Vac/dc in
91 24 V ~ /+
92
6
4
5
T BIAS
Bus speed DIP switch
8
9 600
AUTO
1
0
Bus speed Bus speed is read from Modbus reg-
ister. The device automatically finds
the bit rate, when you set the switch to
position 1 and return it back to position
0. Supported bus speeds are: 9600,
19200, 38400, 57600 and 115200.
3
We reserve the right to make changes to our products without a special notice.