MDS.06R(M)/MDS.10R(M)
Damper Actuator with Emergency Electronic Return - 6/10 Nm - On/O
MOUNTING INSTRUCTIONS
Ø 10...20 mm
5...15 mm
12
34
56
789
www.ismacontrolli.com
iSMA CONTROLLI S.p.A. - Via Carlo Levi 52, 16010 Sant’Olcese (GE) - Italy | [email protected]
page 2DIM304en | 1st Issue | 03/2022
Angle Limitations
LEDS FUNCTIONALITY
WORKING MODE
LEDs STATUS
DESCRIPTION
RED ORANGE GREEN
Supercaps phase
charge
ON OFF OFF Supercaps in charging
ON ON OFF Supercap almost charged
ON ON ON Supercap charged
Working mode ON OFF 2 blinking Clockwise direction movement
ON OFF 3 blinking Counterclockwise direction movement
Emergency return
mode
OFF OFF ON Charge supercaps > 99%
OFF ON OFF Charge supercaps > 66%
ON OFF OFF Charge supercaps > 33%
IP54
The combination of IP54 means, that the product is dust protected (No. 5x) and protected against splash
water (No. x4). Guaranteed for front mounting only. Respect the mounting positions specied in box No. 9.
24 V AC/DC: Connect via safety isolating transformer.
230 V AC: To isolate from the main power supply, the system must incorporate a device which disconnects the pha-
se conductor with at least a 3 mm contact gap).