3. Communication
3.1. RS-485 & CAN setting
Default setting for RS-485: 19200, n, 8, 1 ,for CAN: 125K bps
DIP switch (SW1-SW6) is used for Modbus address(or
CANopen Node ID) setting, default is 1, i.e. all OFF
For example: Modbus address(or CANopen Node ID) is 10,
find the table of DIP switch 1-6 is ON, OFF, OFF, ON, OFF, OFF
SW1-SW6 setting
Setting Modbus-RTU address for communication (1-64)
SW7-SW8 For Baud Rate Setting
PM-3133:Select the different wiring mode
(Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used)
Models
PM-3133 PM-3133-MTCP
Wiring
SW 9 SW 10 SW 1 SW 2
Ethernet default settings
For recovering to default settings, dip
Init/Run Switch (SW 4) to Init position for
10 seconds after power on, the settings
will be changed as default values. Must dip
back to Run position and repower on after settings changed. User also can
recover settings to default value by Modbus command.