Trane Tracer Summit Hardware And Software Installation Manual

Tüüp
Hardware And Software Installation Manual
BMTW-SVN01F-EN
Hardware and Software
Installation
TRACER SUMMIT
Version 16
Hardware and Software
Installation
Tracer Summit
Version 16
BMTW-SVN01F-EN
July 2004
Tracer Summit Version 16
BMTW-SVN01F-EN
BMTW-SVN01F-EN
Tracer Summit Hardware and Software Installation
This guide and the information in it are the property of American Standard Inc. and may not be used or reproduced in whole or in part,
without the written permission of American Standard Inc. Trane, a division of American Standard Inc., has a policy of continuous prod-
uct improvement and reserves the right to change design and specification without notice.
Use of the software contained in this package is provided under a software license agreement. Unauthorized use of the software or
related materials discussed in this guide can result in civil damages and criminal penalties. The terms of this license are included with
the compact disk. Please read them thoroughly.
Although Trane has tested the system described in this guide, no guarantee is offered that the system is error free.
Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any per-
son of such revision or change.
Trane may have patents or pending patent applications covering items in this publication. By providing this document, Trane does not
imply giving license to these patents.
The following are trademarks or registered trademarks of American Standard Inc.: CenTraVac, Dragon, Eagle, Horizon,
IntelliPak, TCM, Tracer, Tracer Summit, Trane, UCP2, VariTrac, VariTrane, CenTraVac, and Voyager.
he following are trademarks or registered trademarks of their respective companies or organizations: ARCNET from
Datapoint Corporation; AutoCAD from Autodesk; BACnet from ASHRAE; Neuron, LonMark, LonTalk, and LonWorks from
Echelon Corporation; Pentium from Intel Corporation; Windows, Windows XP, Internet Explorer, SQL database, and
Microsoft from Microsoft Corporation in the United States and other countries.
Printed in the U.S.A.
© 2004 American Standard Inc.
®
®
BMTW-SVN01F-EN
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully:
WARNING
Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment damage or property damage.
The following format and symbol conventions appear at appropriate sections throughout this manual:
IMPORTANT
Alerts installer, servicer, or operator to potential actions that could cause the product or system to
operate improperly but will not likely result in potential for damage.
This symbol precedes a procedure that consists of only a single step.
Note:
A note may be used to make the reader aware of useful information, to clarify a point, or to describe
options or alternatives.
BMTW-SVN01F-EN i
Contents
Chapter 1 Before Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Tracer Summit System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Modular BCU (BMTW) and the BCU (BMTS) . . . . . . . . . . . . . . . . . . 1
BCU Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
UCM Communication Links—Wiring Requirements . . . . . . . . . . . . . . . . 5
Twisted-Pair Wire—Comm2, Comm3, and Comm4 . . . . . . . . . . . . . 5
Twisted-Pair Wire—Comm5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fiber-Optic Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LAN Communication Links—Wiring Requirements. . . . . . . . . . . . . . . . . 6
Coaxial Cable (10Base2 or “Thinnet”)—Ethernet . . . . . . . . . . . . . . . 6
Unshielded, Twisted-Pair Wire (10BaseT)—Ethernet . . . . . . . . . . . . 6
Coaxial Cable—ARCNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fiber-Optic Cable—Ethernet and ARCNET . . . . . . . . . . . . . . . . . . . . . 7
Optical-Link Loss Budget . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Remote Communication Requirements and Specifications . . . . . . . . . . 9
Communication Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communication Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
BCU Internal Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
PC Workstation Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
PC Workstation Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hardware Requirements for Tracer Summit Standard Software,
Tracer 100/Tracker Communications Package, and Building
Communications Package. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hardware Requirements for Tracer Summit Enterprise
Management Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Software Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Inspection Upon Receipt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Hardware Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Panel Placement (Chapter 2)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Supply Wiring (Chapter 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Assignable Input Wiring (Chapter 3) . . . . . . . . . . . . . . . . . . . . . . . . 13
UCM Wiring (Chapters 4 and 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Network Wiring (Chapter 6). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Contents
ii BMTW-SVN01F-EN
BCU Modem Installation (Chapter 7) . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter 2 BCU Mounting and Power Wiring . . . . . . . . . . . . 15
BCU Mounting and Power Wiring for
North American Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
BCU Mounting for North American Installations . . . . . . . . . . . . . . . 15
Select a Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Verify Conformance to BCU Specifications . . . . . . . . . . . . . . . . 16
Verify Conformance to Clearance Specifications. . . . . . . . . . . . 18
Secure the BCU to the Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Install the Optional Operator Display . . . . . . . . . . . . . . . . . . . . . 19
BCU Power Wiring for North American Installations. . . . . . . . . . . . 19
Verify Compliance with Circuit Requirements . . . . . . . . . . . . . . 19
Connect the AC-Power Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
BCU Mounting and Power Wiring for European
Community Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
BCU Mounting for European Community Installations. . . . . . . . . . 21
Select a Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Verify Conformance to BCU Specifications . . . . . . . . . . . . . . . . 22
Verify Conformance to Clearance Specifications. . . . . . . . . . . . 23
Secure the BCU to the Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Install the Optional Operator Display . . . . . . . . . . . . . . . . . . . . . 24
BCU Power Wiring for European Community Installations . . . . . . 24
Verify Compliance with Circuit Requirements . . . . . . . . . . . . . . 24
Connect the AC-Power Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
BCU Mounting and Power Wiring for International Installations . . . . . 26
BCU Mounting for International Installations. . . . . . . . . . . . . . . . . . 26
Select a Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Verify Conformance to BCU Specifications . . . . . . . . . . . . . . . . 27
Verify Conformance to Clearance Specifications. . . . . . . . . . . . 27
Secure the BCU to the Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Install the Optional Operator Display . . . . . . . . . . . . . . . . . . . . . 28
BCU Power Wiring for International Installations . . . . . . . . . . . . . . 28
Verify Compliance with Circuit Requirements . . . . . . . . . . . . . . 28
Connect the AC-Power Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Preliminary AC-Power Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing and Wiring the BCU Logic Board . . . . . . . . . . . . . . . . . . . . . . 31
BCU Warning Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installing and Removing the BCU Cover . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installing the Optional Operator Display. . . . . . . . . . . . . . . . . . . . . . . . . 33
Contents
BMTW-SVN01F-EN iii
Chapter 3 BCU I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
BCU I/O Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Hardware UIP Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Binary/Pulse Meter Configured UIPs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Thermistor Configured UIPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Current and Voltage Configured UIPs . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Binary Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Chapter 4 UCM Communication-Link Wiring . . . . . . . . . . . . 45
Communication Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
UCM Communication Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Comm2 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Isolated Comm3 Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Non-Isolated Comm3 Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Comm4 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Comm5 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Installing UCM Communication Cards . . . . . . . . . . . . . . . . . . . . . . . 52
Uninstalling UCM Communication Cards . . . . . . . . . . . . . . . . . . . . 53
Communication-Link Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
UCM Communication-Wire Characteristics . . . . . . . . . . . . . . . . . . . 55
Comm5 UCM Communication-Wire Characteristics. . . . . . . . . . . . 56
Recommended Configurations for UCM
Communication-Link Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Termination Resistor placement for
Comm3 and Comm4 links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Termination Resistance Placement for Comm5 Links . . . . . . . . . . 59
Comm5 Physical Link Repeater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
When is the Link Repeater Required? . . . . . . . . . . . . . . . . . . . . 61
Link Repeater Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Link Repeater Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Recommended Wiring Practices . . . . . . . . . . . . . . . . . . . . . . . . 64
Fiber-Optic UCM Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Fiber-Optic Modems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Optical-Link Loss Budget . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Chapter 5 UCM Wiring and Addressing. . . . . . . . . . . . . . . . . 69
CenTraVac Unit Control Panel (UCP1) Interface . . . . . . . . . . . . . . . . . . . 69
Type of Communication Card: Comm2 . . . . . . . . . . . . . . . . . . . . . . 70
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Contents
iv BMTW-SVN01F-EN
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Centrifugal/Absorption/Helical Rotary Chiller (UCP2) Interface . . . . . . 71
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Type of Communication Card: Comm4. . . . . . . . . . . . . . . . . . . . . . . 72
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Commercial Self-Contained (CSC) and IntelliPak CSC Interfaces . . . . . 74
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . . 74
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Horizon Absorption Chiller Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Type of Communication Card: Comm4. . . . . . . . . . . . . . . . . . . . . . . 80
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
IntelliPak Rooftop Unit Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Type of Communication Card: Comm4. . . . . . . . . . . . . . . . . . . . . . . 82
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Lighting Control Panel (LCP) Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . . 87
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Programmable Control Module (PCM) Interface . . . . . . . . . . . . . . . . . . 93
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . . 94
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
RTA-RTW Chiller Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . . 97
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Scroll Chillers: U.S.-built CGA/CGW and
IntelliPak (CGAF) Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . . 99
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Contents
BMTW-SVN01F-EN v
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Terminal Unit Controller (TUC) Interface . . . . . . . . . . . . . . . . . . . . . . . 104
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Type of Communication Card: Comm4 . . . . . . . . . . . . . . . . . . . . . 104
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Thermostat Control Module (TCM) Interface . . . . . . . . . . . . . . . . . . . . 109
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . 109
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Tracer Remote Station (TRS) Interface . . . . . . . . . . . . . . . . . . . . . . . . . .112
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
Type of Communication Card: Non-Isolated Comm3 . . . . . . . . . . .112
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114
Trane Europe Chiller Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . .115
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
Universal Programmable Control Module (UPCM) Interface . . . . . . . .117
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117
Type of Communication Card: Comm4 . . . . . . . . . . . . . . . . . . . . . .117
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
VariTrac II Central Control Panel (CCP) Interface . . . . . . . . . . . . . . . . . 120
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Type of Communication Card: Isolated Comm3 . . . . . . . . . . . . . . 122
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Device Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
VariTrane DDC/VAV UCMs Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Type of Communication Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
VAV Wireless Receiver Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Type of Communication Card: Comm4 . . . . . . . . . . . . . . . . . . . . . 133
Wiring Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Contents
vi BMTW-SVN01F-EN
Voyager Rooftop Unit Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Type of Communication Card: Comm3 or Comm4 . . . . . . . . . . . . 137
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Comm5 UCMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Description of Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Tracer AH540 and Tracer AH541
Air-Handler Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Tracer Loop Controller Interface . . . . . . . . . . . . . . . . . . . . . . . 141
Tracer MP501 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Tracer MP503 I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Tracer MP580 and Tracer MP581 Controllers . . . . . . . . . . . . . . 142
Tracer Zone Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Tracer VV550 and Tracer VV551 controllers . . . . . . . . . . . . . . . 142
Generic LonTalk
®
Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Type of Communication Card: Comm5. . . . . . . . . . . . . . . . . . . . . . 143
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Neuron ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Comm5 Zone Sensor Communication Jack . . . . . . . . . . . . . . . . . . 144
Zone Sensor Communication Stubs. . . . . . . . . . . . . . . . . . . . . 144
Chapter 6 Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Network Communication Configurations . . . . . . . . . . . . . . . . . . . . . . . 147
Tracer Summit PC Workstations . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Connecting Dedicated and Shared Networks. . . . . . . . . . . . . . . . . 149
BACnet—Device IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Network Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Bus Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Ethernet LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
ARCNET LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Star Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Ethernet LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
ARCNET LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Combination Bus/Star Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Ethernet LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
ARCNET LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Calculating Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Ethernet Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Contents
BMTW-SVN01F-EN vii
Configuring an Ethernet Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Installing an Ethernet Card in the BCU Panel . . . . . . . . . . . . . . . . 157
ARCNET Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
ARCNET Single Coaxial Input Interface Card. . . . . . . . . . . . . . . . . 158
ARCNET Single Fiber-Optic Input Interface Card. . . . . . . . . . . . . . 158
ARCNET Three Input Coaxial Hub Card . . . . . . . . . . . . . . . . . . . . . 158
ARCNET Two Coaxial/One Fiber-Optic Hub Card . . . . . . . . . . . . . 159
ARCNET One Coaxial/Two Fiber-Optic Hub Card . . . . . . . . . . . . . 159
Configuring an ARCNET Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
ARCNET Card Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . 159
ARCNET Card DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . 162
Installing an ARCNET Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Installing Coaxial Cable Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
IP Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Preinstallation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Programming the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
BCU (BMTW) Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Setting Up the Broadcast Distribution Table . . . . . . . . . . . . . . . . . 169
Special Situations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Multiple Sites on a Single Shared Network . . . . . . . . . . . . . . 170
BACnet/IP Routers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Connecting a Service Laptop Computer to an
IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
EIA-232 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Installing an EIA-232 Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Configuring a BACnet-Compatible Device . . . . . . . . . . . . . . . . . . . 173
Specifications for EIA-232 Cable Connections. . . . . . . . . . . . . . . . 173
DB-9 Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
DB-25 Connector Pin Assignments. . . . . . . . . . . . . . . . . . . . . . . . . 174
Chapter 7 BCU Modem Installation . . . . . . . . . . . . . . . . . . . 175
Modem Card Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Modem Function Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Installing a Modem Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Chapter 8 Installing Tracer Summit . . . . . . . . . . . . . . . . . . . 179
Installing Tracer Summit using Windows XP or Windows 2000 . . . . 180
Setting UP Network Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Contents
viii BMTW-SVN01F-EN
Installing the Network Adapter Protocol. . . . . . . . . . . . . . . . . . . . . 181
Installing TCP/IP Protocol for BACnet/IP
Communications on Shared Ethernet Networks . . . . . . . . . . . . . 181
Verifying Network Adapter Status and
Protocol for Windows XP or Windows 2000 . . . . . . . . . . . . . . . . 182
Installing Tracer Summit using Windows 98 . . . . . . . . . . . . . . . . . . . . 182
Setting UP Network Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Installing the Network Adapter Protocol. . . . . . . . . . . . . . . . . . . . . 184
Installing TCP/IP Protocol for BACnet/IP
Communications on Shared Ethernet Networks . . . . . . . . . . . . . 184
Verifying Network Adapter Status and
Protocol for Windows 98 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Verifying Adapter Status for Resource
Conflicts for Windows 98. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Determining Available IRQ and I/O Addresses for the ISA and
PCMCIA ARCNET Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Custom Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Installing Tracer Summit using Windows ME. . . . . . . . . . . . . . . . . . . . 188
Setting up Network Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Installing the Network Adapter Protocol. . . . . . . . . . . . . . . . . . . . . 189
Installing TCP/IP Protocol for BACnet/IP
Communications on Shared Ethernet Networks . . . . . . . . . . . . . 189
Verifying Network Adapter Status and
Protocol for Windows ME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Installing Tracer Summit using Windows NT . . . . . . . . . . . . . . . . . . . . 191
Setting UP Network Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Installing the Network Adapter Protocol. . . . . . . . . . . . . . . . . . . . . 191
Installing TCP/IP Protocol for BACnet/IP
Communications on Shared Ethernet Networks . . . . . . . . . . . . . 192
Verifying Network Adapter Status and
Protocol for Windows NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Uninstalling Tracer Summit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Configuring BCUs for BACnet/IP Communications . . . . . . . . . . . . . . . 194
Starting Tracer Summit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Chapter 9 Installing the Daily Operations Tutorial . . . . . . . 195
Chapter 10 BCU Operation and Communication Status . . . 199
LED Indicators for BCU Communication Status . . . . . . . . . . . . . . . . . . 200
LED Codes for BCU Operation Status . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Startup Sequence Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Contents
BMTW-SVN01F-EN ix
New BCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Programmed BCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
BCU Reset Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Clear BCU RAM and Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Clear Database, RAM, and Reset . . . . . . . . . . . . . . . . . . . . . . . 204
Clear Code, Database, RAM, and Reset . . . . . . . . . . . . . . . . . . 205
Chapter 11 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 207
BCU Does Not Respond . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
BCU Locks Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
BCU Does Not Communicate Via Modem . . . . . . . . . . . . . . . . . . . . . . 208
Problems with the Modem and Phone Line. . . . . . . . . . . . . . . . . . 209
Problems with the BCU Modem Programming Setup . . . . . . . . . 209
BCU Does Not Communicate with UCMs. . . . . . . . . . . . . . . . . . . . . . . 209
Communication Failures on Initial Installation . . . . . . . . . . . . . . . 209
Communication Failures that Occur After Initial Installation . . . . 210
BCU Panel Mismatch Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Appendix A Setting DIP Switch Addresses. . . . . . . . . . . . . . . 219
Appendix B BCU (BMTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
BCU (BMTS) Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Installing UCM Communication Cards in a BCU (BMTS) . . . . . . . . . . 226
Communication-Link Field Wiring for the BCU (BMTS) . . . . . . . . . . . 227
Startup and Troubleshooting Sequence for the BCU (BMTS). . . . . . . 229
BCU Power-up Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Effect of Cycling BCU Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
BCU Reset Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Clearing BCU RAM and Reset. . . . . . . . . . . . . . . . . . . . . . . . . . 232
Clear Database, RAM, and Reset . . . . . . . . . . . . . . . . . . . . . . . 233
Clear Code, Database, RAM, and Reset . . . . . . . . . . . . . . . . . . 234
Ethernet Card LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
ARCNET/Hub Card LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Contents
x BMTW-SVN01F-EN
Appendix C Tracer Summit Critical Control System . . . . . . . 237
SQL Database Server Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
PC Workstation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
SQL software installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Installing Tracer Summit Critical Control System using
Windows XP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Setting up network adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Installing the Network Adapter Protocol. . . . . . . . . . . . . . . . . . . . . 239
Installing TCP/IP Protocol for BACnet/IP
Communications on Shared Ethernet Networks . . . . . . . . . . . . . 240
Verifying Network Adapter Status and
Protocol for Windows XP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Initial Startup on SQL database . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Registration considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Reader Response Form . . . . . . . . . . . . . . . . . . . . 255
BMTW-SVN01F-EN 1
Chapter 1
Before Installation
Before installation:
Be sure all items on the packing list are included and are
not damaged.
Familiarize yourself with this guide and any support literature.
Formulate a comprehensive installation plan for the entire Tracer
Summit system.
Tracer Summit System Overview
The Tracer Summit system provides building automation and energy
management functions. The system is capable of monitoring and control-
ling heating, ventilating, and air conditioning (HVAC) equipment and
providing management information and operator override capabilities.
Figure 1 on page 2 shows the options for a Tracer Summit system config-
uration. For a complete list of Trane Comm5 unit controllers, see Table 7
on page 46.
The interface for Tracer Summit uses a graphical format that is accessi-
ble through a PC Workstation. You can connect the PC Workstation and
building control unit (BCU) over an Ethernet LAN or an ARCNET LAN,
or remotely using modems specified by Trane.
The Modular BCU (BMTW) and
the BCU (BMTS)
The main purpose of this installation guide is to provide hardware and
software installation guidance for the modular BCU (BMTW). In the body
of this guide, the term BCU refers to the modular BCU (BMTW). In
Chapter 6, “Network Wiring,” where both BCU models are discussed, the
terms modular BCU (BMTW) and BCU (BMTS) are used.
Appendix B provides hardware installation guidance and troubleshooting
for owners of the BCU (BMTS). In Appendix B, the term BCU refers to
the BCU (BMTS).
Chapter 1 Before Installation
2 BMTW-SVN01F-EN
Figure 1. Tracer Summit System Configuration Options
BCU Components
BMTW-SVN01F-EN 3
BCU Components
The BCU (see Figure 2 on page 4) is a NEMA-1 rated enclosure that
houses the following:
A standard capacity card (required)
An optional high capacity card
A terminator block (TB2)
An optional I/O module with five universal inputs (UIPs), which can
be either analog or binary, and one binary output (BOP)
Four unit control module (UCM) communication card slots for com-
munication links 1, 2, 3, and 4
Three card slots for option cards supplied by Trane, such as Ethernet
cards, ARCNET cards, modem cards, or EIA-232 communication
cards for BACnet interface
A seven-segment LED display for displaying BCU operation status;
the LED operation and codes are described in Chapter 10, “BCU
Operation and Communication Status”
An operator display socket for attaching the optional BCU operator
display
A mini-monitor port for attaching a PC with a straight-through
EIA-232 cable to access built-in diagnostic software; this port is
intended to be used by trained service technicians
The main function of the BCU is to communicate with UCMs, PC Work-
stations, and other BCUs, and to execute all application programs.
Note:
If a BCU has an optional operator display, you need to unplug
the operator display ribbon cable from the operator display
socket and wait 10 seconds before the mini-monitor port
becomes active.
Chapter 1 Before Installation
4 BMTW-SVN01F-EN
Figure 2. Tracer Summit BCU Component Layout
4 AMP MAX
SET UP TOOL
ONLY
ON OFF
ON
S2
BCU I/O module
cable
Optional BCU I/O
module
Seven-segment
LED display
Option card
slots
High capacity
card slot
Standard capacity
card slot
UCM communication
card slots
Operator
display socket
Mini-monitor
port
UCM Communication Links—Wiring Requirements
BMTW-SVN01F-EN 5
UCM Communication Links—
Wiring Requirements
Twisted-Pair Wire—Comm2, Comm3, and Comm4
All unit control modules (UCM) communication-link wiring must be 18-
gauge, shielded, twisted-pair wire with stranded, tinned-copper conduc-
tors.
The maximum length of link wiring (5,000 ft [1,524 m]) is a function of
the total resistance (which is determined by wire length) plus the capaci-
tance between conductors. Wire capacitance between conductors is an
important aspect of the UCM communication link. The wire should have
a maximum capacitance between conductors of 25 pF/ft (78 pF/m) for con-
nections up to 5,000 ft (1,524 m) maximum. Trane recommends that only
low-capacitance wire supplied by Trane be used for UCM communication
links. For UCM communication-link wiring, see Chapter 4, “UCM Com-
munication-Link Wiring.UCM communication and sensor wire is avail-
able through your local Trane commercial sales office.
Twisted-Pair Wire—Comm5
The recommended Comm5 communication-link wiring is 22-gauge,
Level 4, twisted-pair wire. The wire can be either shielded or unshielded.
You can also use 18-gauge, shielded, twisted-pair with stranded, tinned-
copper conductors (Trane “purple” wire).
The maximum wire length for Comm5 communications is 4,500 ft
(1,400 m).
Fiber-Optic Cable
Fiber-optic cable is used for applications involving long distances because
there is little degradation of optic signals. Fiber-optic cable maintains the
integrity of the signal in the presence of various sources of electrical
noise, including lightning, electromagnetic interference/radio-frequency
interference (EMI/RFI), voltage conductors, and ground loops.
Note:
Do not mix wire types on a Comm5 link.
Note:
Use fiber-optic cable for long distances, interbuilding cabling, and/
or other areas of high electrical noise, such as petrochemical
installations, electronic rooms, and hospital nuclear magnetic res-
onance (NMR) or X-ray rooms.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272