TROUBLESHOOTING
Check that the equipment has been correctly installed, i.e. that the
cables are properly stripped, no loose cables, etc., and check that
the DIP switches are correctly set. It is always possible to test run
the drive system using the TEST switch located under the cover next
to terminal 37, see Fig. 4. The switch has two fixed positions, when
MOTOR DIAGNOSIS
Disconnect the supply voltage. Disconnect the motor cables from the
control unit.
Measure the motor resistance between 1–2, 3–4 and 5–6.
The values should be: 15M: 30–90 Ohm; 25M: 5–15 Ohm; 35M: 5–15 Ohm.
The resistance should not differ by more than 5 Ohm between the
phases for 15M, and by no more than 2 Ohm for 25M/35M.
Also check the insulation resistance between 1–3, 1–5, 3–5, 1-earth,
3–earth and 5–earth.
ALARM INDICATION
FAULT CONDITION/ACTION REQUIRED
S E FA U LT
Green LED
flashes slowly
Purging/low
control signal
Check EMX-R by running the drive system with the test switch located next to terminal 37.
The motor should accelerate to its maximum speed. If the motor does accelerate to the maximum
speed when the test switch is activated, the fault is external.
Can 0-10 V (2-10 V) be measured between 33(+) and 34 (-)?
Have + and – been swapped?
Red and green
LED flash rapidly
Pre-alarm,
rotation monitor
The drive system has switched to a softer speed controller because the motor shaft is jerking sharp-
ly. Check that the drive belt is not slipping on the pulley.
Red LED
flashes rapidly Rotation monitor
The exchanger rotor is not rotating; check the drive belt.
The rotor is rotating; check that the indication is given when the magnet passes the rotation sensor,
see the section “Operating indicators”. If not, replace the rotation sensor. Check that the rotor or belt
pulley is not smaller than 630 mm or 63 mm respectively.
Red LED is lit
and green LED
flashes rapidly
Pre-alarm,
overload/motor
protection
The motor protection has been activated due to excessive load. After a cool-down period of 10
minutes, the system restarts automatically. If the overload protection trips 3 times within 120 minutes,
the drive system will be shut down, see also “Overload”. (only red LED is lit).
Red LED is lit Overload/motor
protection
The motor protection has been activated due to excessive load. Check that the
motor cables are connected correctly, see the section on Connection.
Check also that the rotor runs freely and that the diameters of the rotor and pulley are not too large. If
the fault remains, carry out motor diagnosis.
Replace the motor if it is faulty. If the fault does not lie within the motor, replace the control unit.
No LED lit Supply voltage
Missing Check that 230 VAC ±15% is connected to the supply terminal.
Red and green
LED flash slowly
and
alternately
Over voltage The supply voltage exceeds 264 V AC
Under voltage The supply voltage is below 196 V AC
Red and green
LED flash rapidly
and
alternately
Earth connection
in the motor Disconnect the supply voltage, check the connection of the motor cable and check that the correct
motor is connected. If the fault remains, carry out a motor diagnosis.
If the motor is faulty, replace it. If the motor is not faulty, replace the control unit
Red LED
flashes slowly
Short circuit in
the motor.
Circuit break in
the motor
it is in the up position, the motor accelerates to its maximum speed
independent of the control signal, and when it is in the down position
the rotation speed is controlled by the control signal. If the motor does
not reach maximum speed or respond to the controlsignal, check DIP
switches 1-3 and 7 and 8. If the heat exchanger rotates in the wrong
direction, change the setting of DIP switch 6.