ProSoft Technology PS-QS-1x11-0783 Omaniku manuaal

Tüüp
Omaniku manuaal
Document Revision: 3.A
Date: 3/18
T18007
FieldServer ENOTE
Enabling DIP Switches on the QuickServer
FS ENOTE
Page 2 of 11
INTRODUCTION
There are 3 groups of DIP switches available on the QuickServer.
A Bank Address DIP Switch
B Bank Baud rate DIP Switch
S Bank Secondary DIP Switch
SETTING QUICKSERVER DIP SWITCHES
2.1 How to Set the Baud Rate Using DIP Switches
Use the B bank DIP switches to set the baud rate. See DIP switch settings table below
Baud
B0
B1
B2
B3
Auto
1
Off
Off
Off
Off
110
On
Off
Off
Off
300
Off
On
Off
Off
600
On
On
Off
Off
1200
Off
Off
On
Off
2400
On
Off
On
Off
4800
Off
On
On
Off
9600
On
On
On
Off
19200
Off
Off
Off
On
20833
On
Off
Off
On
28800
Off
On
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
115200
Off
On
On
On
For example, to set the baud rate to 57600, the following DIP switch settings apply:
1
Auto-baud is only supported for BACnet MS/TP.
FS ENOTE
Page 3 of 11
To configure DIP switches B0-B3 to adjust the baud rate, the Dynamic Parameters Field needs to be
added to the configuration file.
1. First define a Data Array to hold the baud value read from the DIP switches.
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
, Data_Array_Function
DA_B
, BAUD
, 1
, Dip_Switches_B
2. Make sure a connection is defined in the config file, for example Modbus_RTU.
Connections
Port
, Baud
, Parity
, Data_Bits
, Stop_Bits
, Protocol
R1
, 9600
, None
, 8
, 1
, Modbus_RTU
NOTE: The baud specified here is just a placeholder. The baud rate set on the QuickServer
connection will be as set manually on the QuickServer B bank DIP switches see example
below.
3. Define a dynamic parameter of Function Baud_Rate and Descriptor_Name of the port that the
baud rate has to be set.
Dynamic_Parameters
Function
, Data_Array_Name
, Data_Array_Offset
, Descriptor_Name
Baud_Rate
, DA_B
, 0
, R1
4. Download the config file (see the FS-GUI manual for more details).
5. Restart the FieldServer.
NOTE: The baud rate as set on the DIP switches is only read at start-up. To set a new baud rate,
make the DIP switch changes and restart the QuickServer.
The baud rate as set on the B bank DIP switches can be found in the FS-GUI Data Arrays section as
shown below.
FS ENOTE
Page 4 of 11
The baud rate as set on the B bank DIP switches can also be found in the FS-GUI Connections section
as seen in the following screenshot.
2.2 How to Set the Node_ID Using DIP Switches
Use the A bank DIP switches to set the Node_ID. See the table of A bank DIP switch combinations in the
QuickServer Start-up Guide for a complete list of settings.
For example, to set the Node_ID to 18, the following settings apply:
FS ENOTE
Page 5 of 11
To configure DIP switches A0-A7 to adjust the Device ID, the Dynamic Parameters Field needs to be
added to the configuration file.
1. Define a Data Array to hold the Node_ID Value read from the DIP switches:
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
, Data_Array_Function
DA_A
, UINT16
, 1
, Dip_Switches_A
2. Make sure a connection is defined in the config file, for example Modbus_RTU.
Connections
Port
, Baud
, Parity
, Data_Bits
, Stop_Bits
, Protocol
R1
, 57600
, None
, 8
, 1
, Modbus_RTU
3. Also, make sure the Node is defined for the Node_ID that will be set in the DIP switches.
Nodes
Node_Name
, Node_ID
, Protocol
, Port
Device_A
, 11
, Modbus_RTU
, R1
4. Then define a dynamic parameter of Function Change_Node_ID and Descriptor_Name of the
Node that the ID has to be set.
Dynamic_Parameters
Function
, Data_Array_Name
, Data_Array_Offset
, Descriptor_Name
, Low_Limit
, High_Limit
Change_Node_ID
, DA_A
, 0
, Device_A
, 1
, 255
5. Download the config file (see the FS-GUI manual for more details).
6. Restart the FieldServer.
NOTE: The Node ID is only read on startup. To set a new Node ID, change the DIP switch settings
and restart the QuickServer.
The Node_ID set on the A bank DIP switches is now shown in the FS-GUI Nodes section as seen below.
FS ENOTE
Page 6 of 11
2.3 How to Set the System Station or MAC Address Using DIP Switches
Use the S bank DIP switches to set the MAC_Address. See the S bank table in QuickServer Start-up
Guide for complete list of settings.
When using Change_System_Address, the Descriptor_Name is the Title under the Bridge section.
Use the S bank DIP switches to set the MAC Address. See the DIP switch settings table below.
MAC Address
S0
S1
S2
S3
0
Off
Off
Off
Off
1
On
Off
Off
Off
2
Off
On
Off
Off
3
On
On
Off
Off
4
Off
Off
On
Off
5
On
Off
On
Off
6
Off
On
On
Off
7
On
On
On
Off
8
Off
Off
Off
On
9
On
Off
Off
On
10
Off
On
Off
On
11
On
On
Off
On
12
Off
Off
On
On
13
On
Off
On
On
14
Off
On
On
On
15
On
On
On
On
For example, to set the MAC Address to 11, the following settings apply:
To configure the DIP switches S0-S3 to adjust the BACnet MAC Address, the Dynamic Parameters Field
needs to be added to the configuration file.
1. Define the MAC Address in the Bridge section of the config file:
Bridge
Title
, System_Station_Address
MAC_Address test
, 1
FS ENOTE
Page 7 of 11
2. Define a Data Array to hold the MAC Address Value read from the DIP switches
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
, Data_Array_Function
DA_S
, UINT16
, 1
, Dip_Switches_S
3. Then define a dynamic parameter of Function Change_Node_ID and Descriptor_Name for the
Node that the ID should be set.
Dynamic_Parameters
Function
, Data_Array_Name
, Data_Array_Offset
, Descriptor_Name
, Low_Limit
, High_Limit
Change_System_MAC_Addr
, DA_S
, 0
, MAC_Adress test
, 1
, 15
4. Download the config file (see the FS-GUI manual for more details).
5. Restart the FieldServer.
NOTE: The MAC Address as set on the DIP switches is only read at start-up. To set a new MAC
Address, make the DIP switch changes and restart the QuickServer.
The MAC Address/System_Node_ID set on the S bank DIP switches is now shown in the FS-GUI
Settings section as seen below.
FS ENOTE
Page 8 of 11
PROFILES
3.1 How to Load Different Config Files
The S-Bank DIP switches can be used to set up different profiles each linked to a unique config file.
1. Create the different config files for each profile, hereafter called the Profile Configuration files. In
the example below, the files are called prof1.csv, prof2.csv, prof3.csv.
2. Create a profiles definition config file that will be used to define the profiles. This file can be
named any name and must end with .csv. When downloaded, it will be renamed on the
FieldServer to config.csv. Start by adding a Data Array section that will hold the DIP switch value:
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
, Data_Array_Function
DA_LOAD_CSV
, UINT16
, 1
, ProtoCarrier_ID_S
3. Then create a Config table section and add each Profile Configuration file with a Table Index
Value to match the DIP switch’s value.
Config_Table
Config_Table_Name
, Table_String
, Table_Index_Value
csvfilenames
, prof1.csv
, 1
// Load config 1
csvfilenames
, prof2.csv
, 2
// Load config 2
csvfilenames
, prof3.csv
, 3
// Load config 3
NOTE: In the above example, a DIP switch value of 3 will load the profile that consists of
prof3.csv.
4. Add a dynamic Parameters section that references the data array name and Config Table Name,
defined previously.
Dynamic_Parameters
Function
, Data_Array_Name
, Data_Array_Offset
, Config_Table_Name
, Restart_Method
load_csv
, DA_LOAD_CSV
, 0
, csvfilenames
, On_Change
5. Download the Profiles Definition config file from the Configuration File Transfer page, and
download the individual profile configuration files from the General File Transfer page. See the
FS-GUI manual for details.
6. Make sure to restart the QuickServer for changes to take effect.
FS ENOTE
Page 9 of 11
By setting the DIP switches specified in the following table, the associated profile configuration file will be
loaded at start-up. For example, setting the DIP switch to a value of 2 will load profile configuration file
prof2.csv.
Setting
S0
S1
S2
S3
No change
Off
Off
Off
Off
1
On
Off
Off
Off
2
Off
On
Off
Off
3
On
On
Off
Off
4
Off
Off
On
Off
5
On
Off
On
Off
6
Off
On
On
Off
7
On
On
On
Off
8
Off
Off
Off
On
9
On
Off
Off
On
10
Off
On
Off
On
11
On
On
Off
On
12
Off
Off
On
On
13
On
Off
On
On
14
Off
On
On
On
15
On
On
On
On
The FS-GUI User Messages Information section shows the currently loaded profile as seen below.
FS ENOTE
Page 10 of 11
3.2 How to Clear Profiles
This section describes a dynamic parameter called Clear_Profiles. This will clear the profile database if
any value is written to the data array.
This dynamic parameter is used to clear all profiles that are loaded on start-up. Any value written to the
data array will trigger the clearing of profiles. A restart is required to clear the active configuration if the
profiles have already been loaded.
// Dynamic_Parameters
Function
, Data_Array_Name
, Data_Array_Offset
, Length
Clear_Profiles
, DA_MODE
, 0
, 0
This is the table that connects a profile name with a csv file to load. These profiles can either be loaded
from the web or from a data array (DIP switch included).
// Profiles
Profile_Filename
, Profile_Parameters
, Profile_Selector
, Profile_Name
prof1m.csv
, node_id
, 1
, Veris H8035 MSTP
prof2m.csv
, node_id
, 2
, Veris H8036 MSTP
FS ENOTE
Page 11 of 11
Technical Support
Thank you for purchasing the FieldServer from Sierra Monitor Corporation.
Please call us for any technical support needs related to the FieldServer product.
Sierra Monitor Corporation
1991 Tarob Court
Milpitas, CA 95035
Website: www.sierramonitor.com
U.S. Support Information:
+1 408 964-4443
+1 800 727-4377
Email: smc-support@msasafety.com
EMEA Support Information:
+31 33 808 0590
Email: smc-support.emea@msasafety.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

ProSoft Technology PS-QS-1x11-0783 Omaniku manuaal

Tüüp
Omaniku manuaal