Dettson InterFace paigaldusjuhend

Tüüp
paigaldusjuhend
INTERFACE KIT
K03085
SETUP GUIDE
WARNING
Turn off the breaker of both indoor and
outdoor units before installation.
For all steps, refer to the complete manual of the
thermostat, the furnace and the outdoor unit.
Printed in Canada on 2023-06-13 X00510 Rev.B
100% recycled paper
1 Temperature Sensor Installation
1. Attach the provided temperature
sensor to the evaporator coil at mid-
height on the cross-over.
2. Get the wire through the opening of
the 3/8” refrigerant line.
3. Cut the connector and skin the
conductors. Add wire length if
necessary.
4. Connect the two conductors to T1
and TC on the interface board. The
polarity is not important.
2 Interface Board Location
For Dettson furnaces, install the interface board at the proposed location using the provided spacers.
Use the provided deflector in Chinook gas furnaces, or for non-Dettson furnaces.
CHINOOK
Compact Chinook 15K-30K-45K-105K-120K Chinook 60K-75K
SUPREME CAH050
Modulating
2
3 Wiring
3.1 OPTION 1 - Communicating System
Setup with Modulating Chinook or Supreme
1. Connect COND-1,COND-2 and COND-3 on the interface board to the 1,2and 3respectively
on the outdoor unit.
2. Connect the thermostat wires 1,2,Rand Cto the furnace.
3. Connect the RJ-11 wire (A00443) between the interface and the furnace control board.
4. Optional ERV/HRV interlock:
(a) Connect the ERV/HRV unit (dry contact) between the Rand Gterminals on the interface
board.
(b) The desired airflow can be adjusted through the thermostat settings.
5. The temperature sensor must be properly installed on the‘ indoor coil (section 1) and connected
between T1 and TC.
In this configuration, the interface board will gather information from both the outdoor unit and the
furnace in order to adjust the fan speed to the capacity of the outdoor unit.
Balance point adjustment
Refer to the thermostat manual to adjust the balance point (temperature below which auxiliary heat
will be used).
3
3.2 OPTION 2 - Legacy 24V System
Setup with non-modulating furnaces
1. Connect COND-1,COND-2 and COND-3 on the
interface board to the 1,2and 3respectively on the
outdoor unit.
2. Connect the thermostat wires as shown on the
diagrams.
3. Make sure to properly connect the heat singals:
(a) Output W1 and W2 of the thermostat to the W1
and W2 inputs of the interface board.
(b) For single-stage thermostats, connect to W2 on
the interface board.
(c) If using a thermostat with heat pump control (O/B
signal), make sure it is configured to match the
thermostat signal (dip switch S1-5).
(d) W1 out and W2 out of the interface board goes to
W1 and W2 of the furnace.
4. If the DH signal is connected, remove the DH jumper
on the interface board (located near the DH terminal).
5. The temperature sensor must be properly installed on
the indoor coil (section 1) and connected between T1
and TC.
6. Adjust the balance point using the dip switches S1-2,
S1-3 and S1-4 on the interface board.
Heat Pump Signal
S1-5 Signal
OFF B
ON O
Wiring with thermostat for heat pump control
4
Wiring with conventional thermostat
Balance point adjustment
S1-2 S1-3 S1-4 Balance Point
OFF OFF OFF -30°C (-22°F)
OFF OFF ON -20°C (-4°F)
OFF ON OFF -15°C (5°F)
OFF ON ON -10°C (14°F)
ON OFF OFF -5°C (23°F)
ON OFF ON 0°C (32°F)
ON ON OFF 5°C (41°F)
ON ON ON HP heat only
5
4 Settings
Location of DIP Switches
4.1 Capacity adjustment
The capacity of the outdoor unit connected to the interface board must be selected using the dip
switches SW1.
SW1-1 SW1-2 SW1-3 SW1-4 Capacity (btu/h)
ON OFF OFF OFF 9k
OFF ON OFF OFF 12k
ON ON OFF OFF 18k
OFF OFF ON OFF 24k
ON OFF ON OFF 30k
OFF ON ON OFF 36k
4.2 Mode A/C only
To run the outdoor unit in “Air Conditioner” mode (no heat), turn ON the dip switch S1-1.
S1-1 Mode
OFF AC & HP
ON AC only
4.3 Zoning System
When installed with the Dettson Smart Zoning System, the airflow limitation per zone can be disabled
by turning the dip switch S1-5 to ON. This is not recommended.
6
5 Troubleshooting
5.1 Testing the Unit
Once everything is correctly installed, turn the power and:
1. The Green LED on the interface board should be blinking once every two seconds.
2. The Orange LED on the interface board should be blinking once every two seconds.
3. The communicating thermostat will find the heat pump.
4. Set the thermostat to “COOL” mode and adjust the set point to a lower value than the actual
room temperature.
5. The Blue LED on the interface board should turn on and both the furnace and the outdoor unit
should start within 5 minutes.
5.2 LED Codes
Green LED
There are two green LEDs.
The upper green LED should blink steadily, otherwise it indicates an error code from the outdoor unit.
The lower green LED, along with the orange LED next to it, will indicate the current error code (see
table on next page).
Orange LED
The orange LED, along with the green LED next to it, will indicate the current error code (see table
on next page).
Yellow LED
In communicating mode, the yellow LED should be blinking by short bursts. If not, there is a
communication issue with the furnace. RJ-11 cable and wires 1 and 2 should be checked.
In legacy mode (24V), this LED should stay off.
Blue LED
The blue LED will turn on when there is a call for cooling from the thermostat.
Red LED
The red LED will turn on when there is a call for heating from the thermostat.
White LED
The white LED will turn on when there is a call for ERV fan or dehumidification. In communicating
mode, this LED will blink when there is a dehumidifiaction call.
7
Error Codes
Green LED Orange LED Status
Off Off No power (check R & C)
Off Blink Outdoor fan speed control error
Off Rapid Compressor protection error
Off On IPM protection
Blink Off Communication error with indoor unit
Blink Blink Normal operation
Blink On Communication error with outdoor unit
Rapid Off Low pressure protection
Rapid Blink Compressor high temperature (overheat)
Rapid Rapid Voltage protection
Rapid On Current protection
On Off Outdoor condenser temperature sensor error
On Blink Outdoor ambient temperature sensor error
On Rapid Outdoor condenser high temperature
On On Compressor exhaust temperature sensor error
8
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Dettson InterFace paigaldusjuhend

Tüüp
paigaldusjuhend

teistes keeltes